Danfoss Turbocor Compressor Chiller KSA:Engineering Guide to Oil-Free Magnetic-Bearing Chillers in Saudi Arabia
Component & Niche Guide | ASPAR Engineering | Reviewed October 2026
Direct answer Danfoss Turbocor is an oil-free centrifugal compressor platform that uses magnetic bearings, a permanent-magnet motor, an integrated variable-speed drive and electronic controls. It can be used inside air-cooled, water-cooled and evaporatively cooled chillers. For Saudi projects, the important question is not simply whether a chiller contains a Turbocor compressor; the complete chiller must be selected for the actual cooling duty, project ambient or condenser-water conditions, refrigerant, electrical supply, controls, redundancy, acoustics, maintenance strategy and local service requirements. High-lift Turbocor TTH/TGH models are specifically positioned by Danfoss for demanding high-lift applications such as air-cooled chillers in hot ambient climates, but project suitability must be verified through the chiller OEM selection and operating map. |
The search for a “Danfoss Turbocor compressor chiller KSA” is usually not a search for a loose compressor. Engineers, consultants, facility owners and technical buyers are typically trying to identify a complete chiller that uses Turbocor technology and determine whether that chiller is suitable for Saudi operating conditions. This article therefore treats Turbocor as a critical component inside a larger HVAC system and focuses on how to evaluate the complete solution.
What is a Danfoss Turbocor compressor?
Danfoss Turbocor compressors are oil-free centrifugal compressors developed for HVAC and chiller applications. Danfoss describes the platform as using magnetic bearings, a high-speed permanent-magnet motor, variable-speed drive technology and intelligent electronic controls. Because the rotor is magnetically supported while operating, the compressor does not require the conventional oil-management system used by many screw and traditional centrifugal compressors.
The compressor technology can be applied in air-cooled, water-cooled and evaporatively cooled chillers. The exact chiller performance still depends on heat-exchanger design, refrigerant, compressor quantity, condenser conditions, controls and the OEM operating envelope.
Official technology reference: Danfoss Turbocor compressor platform

Figure 1. Turbocor compressor technology is one part of the complete chiller system.
The main Turbocor compressor families engineers may encounter
Danfoss publishes several Turbocor product families. Product ranges change as compressor generations and refrigerant options evolve, so the current Danfoss selection data should always control. The following table summarizes the current publicly listed portfolio at a high level.
Series | Public nominal range | Refrigerant examples | Engineering relevance |
TGS | Approx. 65-150 TR / 230-520 kW nominal | R1234ze or R515B | Air- and water-cooled, low-lift applications; low-GWP focus. |
TTS | Approx. 85-200 TR / 300-700 kW nominal | R134a or R513A | Common oil-free centrifugal range for air- and water-cooled chillers, depending on model. |
TTH / TGH | Approx. 107 TR / 376 kW and 82 TR / 288 kW nominal | R134a/R513A or R1234ze/R515B | High-lift platform; particularly relevant to demanding air-cooled and hot-ambient applications. |
VTX | Up to about 450 TR / 1600 kW nominal per compressor | R134a | Higher-capacity oil-free compressor optimized for water-cooled / evaporatively cooled chiller applications. |
Important Do not select a chiller from compressor nominal tonnage alone. Compressor capacity is not the same as complete chiller net capacity at the Saudi project design condition. The chiller OEM selection must include heat exchangers, approach temperatures, ambient or condenser-water conditions, compressor staging and all relevant options. |
Why Turbocor technology is attractive for Saudi chiller projects
1. Oil-free magnetic bearings remove the compressor oil circuit
Traditional oil-lubricated compressor systems require oil pumps, heaters, filters, separators, return paths and maintenance procedures. Turbocor eliminates the compressor lubrication oil system. Danfoss states that this simplifies chiller architecture and reduces oil-related maintenance. It also avoids heat-exchanger performance degradation associated with oil contamination of refrigerant-side surfaces.
2. Variable-speed operation supports strong part-load efficiency
The integrated variable-speed architecture allows the compressor to reduce speed as load and lift fall. This is especially relevant to commercial buildings, data centers, hospitals and mixed-use facilities where chillers spend many operating hours below peak design load. The actual annual saving depends on the plant load profile, water temperatures, condenser conditions, staging logic and control sequence.
3. Low starting-current burden can help constrained electrical systems
Danfoss technical literature describes a built-in soft-start architecture with compressor startup inrush of about 2 A. This value applies to the compressor architecture cited by Danfoss; it must not be misrepresented as whole-chiller current. The complete chiller still has running current, controls, fans, pumps and other auxiliaries. For generator-backed or electrically constrained projects, request whole-chiller starting current, starting kVA, harmonics and restart sequence from the chiller OEM.
4. Lower sound and vibration can benefit sensitive projects
Magnetic bearings and high-speed direct-drive operation eliminate conventional rolling-element bearing contact during normal operation. Danfoss publishes low sound levels for Turbocor compressor platforms, while chiller OEMs may also use low-noise fans, acoustic panels and control strategies. Hospital, hotel and data-center projects should still be evaluated using complete chiller acoustic data at the actual receiver—not compressor sound data alone.
5. Multiple compressors can support staging and redundancy
Many oil-free chillers use multiple smaller Turbocor compressors rather than one large fixed-speed compressor. This can support staged capacity control and may offer partial redundancy when the chiller and controls are designed accordingly. The consultant should verify the actual failure mode, remaining capacity and control strategy rather than assuming N+1 performance from compressor count alone.
Why KSA applications need more than a standard Turbocor selection
Saudi Arabia adds several application constraints that can dominate chiller selection. A compressor technology may be suitable in principle while the complete chiller fails the project duty because of condenser air temperature, heat-exchanger sizing, power quality, dust loading, physical layout or controls.
KSA design issue | What should be verified |
High outdoor temperature | Net cooling capacity and input power at the actual condenser-entering air temperature; use the OEM operating map and application selection. |
High lift for air-cooled chillers | Whether the selected Turbocor family and chiller design can sustain the required pressure ratio and leaving-water condition. |
Dust and coil fouling | Condenser coil access, filtration/screens if used, cleaning strategy, fin spacing and maintenance access. |
Rooftop recirculation | Clearances, parapets, acoustic screens, adjacent chillers and wind effects; consider CFD when geometry is complex. |
Electrical system | Project voltage/frequency, full-load current, harmonics, starting sequence, generator compatibility and restart logic. |
Corrosion environment | Coil and cabinet protection for coastal or industrial sites; confirm impact on heat transfer and warranty. |
Service capability | Trained service resources, diagnostics, spare electronics, compressor replacement strategy and response time. |
Low-GWP refrigerants | Compatibility of compressor and chiller design, safety classification, project codes and refrigerant availability. |
Turbocor high-lift compressors: why TTH/TGH matters in hot climates
Danfoss specifically positions the TTH/TGH oil-free magnetic-bearing series for high-lift applications, including air-cooled chillers in hot ambient climates, heat recovery, heat pumps and thermal storage. This makes the series particularly relevant to Saudi applications where a large temperature difference may exist between evaporating and condensing conditions.
However, “high lift” should not be treated as a blanket 50°C or 55°C chiller rating. The compressor is only one part of the refrigeration system. The chiller OEM must still prove the operating envelope, condenser capacity, net cooling duty, power input, control margin and reliability at the specified Saudi design condition.
Official reference: Danfoss Turbocor TTH/TGH high-lift compressors
How Turbocor compressors appear in complete chiller products
Turbocor compressors are components supplied to chiller manufacturers rather than complete chillers by themselves. One public example is Smardt’s T-Class water-cooled chiller literature, which documents use of Turbocor TTS compressors in its oil-free chiller platform. Smardt has also published air-cooled chiller literature describing the use of Danfoss Turbocor oil-free compressors.
This is useful evidence of real OEM integration, but it should not be used to assume that every Smardt, TICA or other oil-free magnetic chiller model uses the same Turbocor series or refrigerant. Exact compressor type, quantity and controls must be confirmed from the offered chiller submittal.
Public OEM example: Smardt T-Class water-cooled chiller overview
Selection workflow for a Danfoss Turbocor chiller in KSA

Figure 2. Project-specific selection workflow for Saudi applications.
1. Define the actual cooling duty at peak and minimum load, chilled-water temperatures, design flow and redundancy requirement.
2. Define the actual condenser condition: outdoor air for air-cooled equipment, or condenser-water entering temperature for water-cooled equipment.
3. Identify whether the application is low-lift or high-lift and whether the selected Turbocor series is appropriate for that envelope.
4. Obtain a complete chiller application selection showing net capacity, total input power, efficiency, compressor staging, operating limits and design margins.
5. Check electrical data including whole-chiller current, power factor, harmonic performance, starting behavior and restart sequence.
6. Check noise, vibration, dimensions, weight, service clearances, hydronic pressure drop and BMS integration.
7. Confirm service capability, diagnostics, spare parts and maintenance documentation for the offered model in Saudi Arabia.
8. Approve only the exact offered chiller configuration and current submittal—not a generic Turbocor data sheet.
What data should be required in a Turbocor-based chiller submittal?
Submittal item | Minimum information to request |
Compressor identity | Exact Turbocor model/series, quantity per chiller, refrigerant and software/controls generation where applicable. |
Project capacity | Net cooling capacity at project entering/leaving water temperatures and actual condenser condition. |
Power and efficiency | Total unit input kW, full-load efficiency and applicable part-load metric with rating basis clearly stated. |
Operating map | Maximum/minimum ambient or condenser-water conditions, leaving-water limits, unloading range and high-lift restrictions. |
Electrical | Voltage/frequency, MCA/MOCP where applicable, running current, start behavior, harmonics and power factor. |
Controls | Compressor staging, anti-surge/control logic, restart after power loss, BMS protocol and trend points. |
Mechanical | Dimensions, operating/shipping weight, nozzles, evaporator/condenser pressure drop, service clearances and lifting data. |
Acoustics | Complete chiller sound power or sound pressure data under a defined test/rating basis. |
Maintenance | OEM preventive-maintenance schedule, diagnostic tools, fault history access and required technician competency. |
Certification | Project-required AHRI/Eurovent/other certification plus project-specific application data where standard ratings do not represent the KSA design point. |
Maintenance: oil-free does not mean maintenance-free
Turbocor technology removes the conventional compressor oil circuit and many oil-related service tasks, but a Turbocor-based chiller still requires structured maintenance. The complete maintenance plan should include heat exchangers, water quality, condenser coils or cooling towers, refrigerant charge, electrical connections, sensors, controls, VFD/electronic modules, chilled-water flow, pumps, filters/strainers, BMS alarms and the chiller OEM’s specified inspections.
Danfoss also provides diagnostic and service tools for Turbocor compressors. The service strategy should be based on the chiller OEM manual and the exact compressor generation, not on a generic assumption that magnetic bearings require no attention.
Maintenance rule “No oil changes” is a valid maintenance advantage of an oil-free compressor architecture. “No maintenance” is not. The project owner still needs a preventive-maintenance plan for the complete chiller and plant. |
Electrical and controls considerations
Because Turbocor compressors use integrated power electronics and variable-speed control, the electrical design should review harmonics, source impedance, generator interaction, earthing, protective coordination and restart behavior. In mission-critical applications, the consultant should define how chillers, pumps and cooling-tower or condenser-fan loads recover after a utility interruption.
The low compressor-start current can be valuable, but whole-chiller data remains essential. For a plant using several compressors per chiller, confirm whether starts are staggered and how quickly available cooling capacity returns after power restoration.
Refrigerant choice: confirm the compressor and chiller together
Current Turbocor families are available with several refrigerants, including R513A, R1234ze and R515B, while some products continue to use R134a. Refrigerant selection affects compressor capacity, heat-exchanger sizing, safety classification, operating pressure, local code requirements and long-term refrigerant strategy. Do not substitute a refrigerant based only on compressor compatibility; the complete chiller must be designed, rated and approved for it.
Where this technology is especially relevant
· Data centers and mission-critical facilities where part-load efficiency, restart behavior, redundancy and low maintenance are important.
· Hospitals and healthcare facilities where low sound, stable operation and lifecycle reliability are important selection factors.
· Commercial buildings and mixed-use developments with long annual operating hours and variable cooling loads.
· Retrofits where low starting-current burden, compact compressor architecture or lower maintenance complexity may solve an electrical or plant-room constraint.
· Industrial and process applications where precise capacity control and long operating hours justify detailed lifecycle analysis.
Common mistakes when specifying a “Turbocor chiller”
· Specifying only “Danfoss Turbocor compressor” without defining the required chiller duty and site conditions.
· Assuming any Turbocor series is suitable for Saudi high-ambient air-cooled duty without checking lift and the OEM operating map.
· Comparing compressor nominal capacity with complete chiller net capacity.
· Using the compressor’s low startup current as if it were the whole-chiller electrical starting current.
· Calling an oil-free chiller “maintenance-free.”
· Ignoring condenser airflow, rooftop recirculation, dust and coil cleaning requirements.
· Assuming every oil-free magnetic chiller uses the same Turbocor compressor family or refrigerant.
· Approving the chiller without confirming local service capability, diagnostics and parts strategy.
· Using marketing part-load efficiency claims without a common rating basis or project load profile.
Copy-ready consultant checklist: Turbocor-based chiller for Saudi Arabia
· ☐ Required net cooling duty: ____ kW / TR at CHW entering ____°C, leaving ____°C, flow ____ L/s.
· ☐ Condenser design condition: air ____°C DB entering condenser / condenser water ____°C entering.
· ☐ Site elevation: ____ m. Project application: commercial / hospital / data center / industrial / other.
· ☐ Chiller architecture: air-cooled / water-cooled / evaporatively cooled.
· ☐ Turbocor compressor series/model and quantity clearly stated: Yes / No.
· ☐ Refrigerant and safety classification stated: Yes / No.
· ☐ Net capacity and total chiller input power at project condition verified: Yes / No.
· ☐ Full-load and part-load rating basis stated: Yes / No.
· ☐ Maximum/minimum operating envelope and high-lift limits provided: Yes / No.
· ☐ Whole-chiller electrical data, harmonics and restart sequence provided: Yes / No.
· ☐ Sound data and test/rating basis provided: Yes / No.
· ☐ Condenser airflow / cooling-tower requirements and service clearances coordinated: Yes / No.
· ☐ BMS points, alarms, trends and communications protocol defined: Yes / No.
· ☐ OEM maintenance schedule, diagnostic access, spare parts and service plan provided: Yes / No.
· ☐ Final current submittal reviewed against the approved project duty: Yes / No.
How ASPAR Engineering can support a Turbocor-based chiller project
ASPAR Engineering as a solution provider A compressor platform is only one part of the engineering decision. ASPAR Engineering can support consultants, contractors and owners in evaluating the complete chiller solution against the project cooling duty, Saudi climate conditions, plant layout, electrical system, acoustics, controls, maintenance strategy and lifecycle objectives. ASPAR’s role is to help the project team move from a component-level requirement toward a coordinated HVAC solution. |
For projects considering oil-free magnetic-bearing chillers, ASPAR can support equipment selection and technical comparison through its chiller solutions portfolio. Where the chiller must be integrated into a wider system, ASPAR’s MEP engineering design services can support load calculations, plant configuration, electrical coordination, BOQs and specifications.
For operating facilities, ASPAR’s HVAC operation and maintenance services can support system assessment, troubleshooting, preventive maintenance, retrofit planning and performance improvement. Testing and commissioning services can be used to verify that the installed chiller, pumps, controls and associated systems operate according to the approved design intent.
For mission-critical facilities, ASPAR’s data-center MEP and cooling solutions provide a broader framework for redundancy, control integration, restart strategy, energy performance and lifecycle support.
Need help selecting an oil-free magnetic-bearing chiller for a Saudi project? Explore ASPAR Chiller Solutions | Discuss Your Project with ASPAR Engineering |
Relevant ASPAR Engineering pages
· Chiller Solutions in Saudi Arabia — Oil-free magnetic chillers and other chiller technologies for project-specific selection.
· TICA HVAC Solutions in Saudi Arabia — ASPAR’s TICA HVAC technology and oil-free chiller context.
· MEP Engineering Design — HVAC design, load calculations, electrical coordination, BOQs and specifications.
· HVAC Operation & Maintenance — Preventive maintenance, troubleshooting, retrofits and system-performance support.
· MEP Testing & Commissioning — Performance verification and commissioning of integrated MEP systems.
· Data Center MEP & Cooling Solutions — Mission-critical cooling, redundancy, controls and energy-performance context.
· Contact ASPAR Engineering — Project-specific technical enquiry and consultation.
Frequently asked questions
What is a Danfoss Turbocor chiller?
It is a chiller manufactured by an HVAC OEM that uses one or more Danfoss Turbocor oil-free centrifugal compressors. Danfoss supplies the compressor technology; the complete chiller design, rating, heat exchangers, controls and certification are the responsibility of the chiller OEM.
Are Danfoss Turbocor compressors suitable for Saudi Arabia?
They can be suitable when integrated into a chiller selected for the actual Saudi project conditions. Danfoss specifically positions TTH/TGH compressors for high-lift applications including air-cooled chillers in hot ambient climates. The exact chiller must still be verified through the OEM operating map and application selection.
Does a Turbocor compressor contain oil?
The Turbocor compressor architecture is oil-free and uses magnetic bearings. The complete chiller may still contain other service fluids and components that require maintenance.
What is the starting current of a Turbocor compressor?
Danfoss literature describes startup inrush of about 2 A for the compressor soft-start architecture. This is compressor-level information, not the total chiller starting current. Whole-chiller electrical data must be obtained from the OEM.
Which refrigerants are used with Turbocor compressors?
Current public Danfoss product information includes R513A, R1234ze, R515B and some R134a applications, depending on compressor family and model. The selected chiller must be specifically designed and approved for the refrigerant.
Is a Turbocor chiller maintenance-free?
No. Oil-related compressor maintenance is reduced, but the complete chiller still requires maintenance of heat exchangers, coils or cooling towers, water circuits, controls, sensors, refrigerant charge, electrical systems and other components.
Is Turbocor better than a screw compressor?
The technologies have different strengths. Turbocor can provide oil-free operation, variable-speed part-load efficiency, low startup current and reduced oil-system maintenance. Screw compressors can be appropriate for other operating envelopes, capacities and service strategies. The project duty and lifecycle requirements should determine the choice.
Can ASPAR Engineering help select a Turbocor-based chiller in KSA?
ASPAR Engineering publishes chiller solutions, MEP design, commissioning, operation and maintenance, and data-center cooling services. ASPAR can support project-specific evaluation of oil-free magnetic-bearing chiller solutions without implying that every ASPAR oil-free chiller uses a specific Danfoss compressor model.
Conclusion
For Saudi projects, the value of Danfoss Turbocor technology is best understood at component level and then verified at system level. Magnetic bearings, oil-free operation, variable-speed control, low compressor starting current and strong part-load capability can create meaningful engineering advantages. But the compressor brand alone does not determine whether a chiller is suitable for a Riyadh rooftop, a Jeddah data center, a hospital plant room or an industrial cooling application.
The correct workflow is to define the real project duty, identify the required lift and condenser condition, choose a suitable Turbocor compressor family through the chiller OEM, verify the complete chiller performance and electrical data, and then coordinate airflow, hydronics, controls, maintenance and commissioning. That turns a niche component search into a reliable project-specific HVAC solution.
Sources and technical references
Technical note Public product ranges, refrigerants and model availability can change. Final procurement, design and construction decisions should use the current chiller OEM selection, compressor data, project specifications, local Saudi requirements and approved submittals for the exact offered configuration. |